Digital Communications Interfaces ________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
7-34
14.
Reset All
: This button, when clicked, will reset the counters of the associated comms
interface.
Note
: Reset the following counters to zero by the “Reset All” button.
15.
Errored Seconds
: Provides a count of the total number of errored seconds since the last
reset.
16.
Errors per Second:
Provides a count of the number of errored words that occurred over
the last second.
7.5.5 Status Direct Fiber Digital Comms
This page allows the user to view the status of different parameters of the Direct Fiber comms
interface module.
1
2
9
3
4
5
6
7
8
10
11
12
14
15
13
STATUS > Digital Comms > Slot # - FIBER
Figure 7-24. Status Screen Direct Fiber Digital Comms
1.
Service
: This value indicates the module is ‘enabled’ for service.
Settings to create this Status
Status Message
Mode
Enable
Module Mapping
“Forced Disabled”
Normal
Disabled
“Enabled”
Normal
Auto
mapped to any
Bus/timeslot
“Disabled”
Normal
Auto
not mapped to any
Bus/timeslot
“Aux Channel”
Aux Channel