Power Line Carrier ____________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
5-14
FSK Configuration
– Advanced
Menu location: Configuration > PLC > (Advanced).
The following settings are for advanced users only. HPS/RFL recommends that the factory be
contacted before any changes are made to this web page.
1
3
4
5
Advanced
tab
2
6
7
8
Function buttons
See 5.4.1.4
9
Figure 5-7. FSK Configuration, Advanced
1.
Discriminator Energy Threshold:
This setting indicates the differential in signal level
between guard and trip frequencies required to declare a change of state. Should be set
to 15dB for proper operation. The range is from 0dB to 100dB in 1dB increments.
2.
RX AGC Setpoint:
Determines the headroom allowed in the analog section of the
receiver when commissioned. Should be set to 30.
3.
Minimum Rx Level:
Determines the minimum point at which a trip can be
instantaneously received. The FSK RX threshold sets the absolute level, this sets the
instantaneous level. The range is 6 to 100 in increments of 1. Must be set to 11.
4.
Trip Rx Threshold:
This setting determines the minimum amount of energy (below the
commission point) at which tripping is allowed. It should be set to 25 for most
applications. The range is 0 to 100 in increments of 1.