Power Line Carrier ____________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
5-12
1
2
3
4
5
10
6
7
8
Save button
RX Frequency Table
TX Frequency Table
General tab
9
11
12
Figure 5-6. FSK Configuration
Transmitter Enable:
1.
Transmit Center Frequency:
Sets the TX center frequency from 30kHz to 500kHz in
0.125kHz increments. Refer to
6.3.3
for instructions on setting the RF Power Output
Filter (TX Filter) jumpers.
2.
TX Shift:
Sets the TX shift from the center frequency in increments of 2.
3.
TX Guard Level:
Sets the transmit guard level. The selections are 1W, 3W or 10W.
4.
TX Trip Level:
Sets the transmit trip level. The selections are 1W, 3W or 10W.
5.
TX Trip 1 Shift Direction:
In 2F mode selects the trip direction. The options are “Shift
Up” or “Shift Down.” In 3F mode selects the “Trip1” direction, the “Trip2” direction is
automatically set to the opposite direction. The options are “Shift Up” or “Shift Down.”
Receiver Enable:
6.
RX Center Frequency:
Sets the RX center frequency from 30kHz to 500kHz in
0.125kHz increments.
7.
RX Bandwidth:
Set to 200Hz, 500Hz or 1000Hz.
Note:
For 3F systems you must select the bandwidth between the center frequency and
either the “Shift Up” or “Shift Down” frequency.
Not the total bandwidth from shift