Digital Communications Interfaces ________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
7-28
16.
Path Code Violations
: This is a Path Code Violations since the last reset. Counts bad
words based on Cyclic redundancy Check bits (CRC) in the T1/E1 data stream.
17.
Frames Out-of-Sync
: This is a count of the Frames Out-of-Sync since last reset. Counts
the number of frame bit errors in Super Frame Mode. For each invalid frame message
the counter will increment.
18.
Errored Seconds
: This is the count of the Errored Seconds since the last reset. The
counter increments a maximum of one for each second that contains errors.
19.
Severely Errored Seconds
: This is the count of Severely Errored Seconds since the last
reset. Counts the number of seconds a T1/E1 major alarm was active. The counter
increments a maximum of one for each second that contains errors.
7.5.2 Status C37.94 Digital Comms
This page allows the user to view the status of different parameters of the C37.94 comms interface
module.
1
2
9
3
4
5
6
7
8
10
11
12
14
15
13
STATUS > Digital Comms > Slot # - C37.94
Figure 7-21. Status Screen C37.94 Digital Comms
1.
Service
: This value indicates the ‘enabled’ status of the module.
Range:
Settings to create this Status
Status Message
Enable
Module Mapping
“Forced Disabled” Disabled
“Aux Channel”
Aux Channel
“Enabled”
Auto
Any Bus/timeslot
“Disabled”
Auto
Not mapped to any
Bus/timeslot