System Configuration __________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
4-63
Table 4-8. DNP Type Configuration Field Descriptions
Name
Description
Values
Index
Indicates to the user whether or not it is set up for
Auto or Manual indexing. This is set on the Config
> DNP > General page.
Auto, Manual
“All”
control -
Class
The Class selected with the “All” button applies to
all points in the table. If “Enable” is unchecked the
Class selection tool is disabled.
Class 1, Class 2, Class 3, Class 0
“All”
control -
Enable
Selecting the Enable or Disable from the All button
applies to all points in the table.
Enable, Disable
Index
This column shows the index value of the point in
the same row. For Auto, the Index field will auto-
update as points are enabled and disabled, to indicate
to the user that the point list is being dynamically
assigned on the points which are enabled/disabled.
Control disabled if: Indexing mode = Auto
Auto- the index number is assigned and cannot
be modified.
Manual- any number within the valid range
defined by manual indexing rules described
above, as long as the index value is not already
assigned to another point of the same type.
Parameter
#
This is the fixed HPS/RFL GARD Pro system
parameter #. For example, HMIOUT60, while it can
have an index value manually assigned, will always
have parameter # of 60. This field allows the user to
assign connections between DNP points and their
index numbers, back to the HPS/RFL GARD Pro
system and logic.
System/functional module parameter number.
Label
For functional module points this field is a user
entered label. For system logic points this field is
read only. SOE Trigger labels can be changed in the
Configuration > SOE page, and HMI labels can be
changed in the "Advanced > HMI Bits page
System logic points: HMI labels and SOE labels
Functional module points: Default, User edit
Class
This determines the class of the associated DNP
point in the same row. Default class:
•
Type 1 - Class 1
•
Type 10 - Class 1
•
Type 20 - Class 3
•
Type 30 - Class 2
The default is Class 1 and control is disabled if:
DNP Point enable = “OFF”
Class 1, Class 2, Class 3, Class 0.
Enable
This control determines whether or not the associated
point will be included in the DNP engine for
reporting.
The default is “Off”.
On, Off (check box control, as shown in
screenshot)
Default
Index
Assigns point index values according to GARD Pro
defaults.
Available only with Point Index Mapping set to
Manual (Configuration > DNP > General)
GARD Pro assigns HMIOUT bits from 0 to 63
according to the HMIOUT bit number.
Cancel
Resets any changes to the values when the page was first opened. Clicking this button will bring up a
confirmation dialog.
This button is disabled if no changes were made.
Save
This control will write the changes made to the settings in the web page. Clicking this button will bring
up a confirmation dialog.
This button is disabled if no changes were made.