Power Line Carrier ____________________________________________________________________
RF-MCGARDPRO
Hubbell Power Systems, Inc.
–
RFL™
Products
July 1, 2022
©2022 Hubbell Incorporated
5-22
On/Off Configuration
– General
Menu location: Configuration > PLC (General).
Ensure that the “General” tab is clicked. If not already enabled, the module should be enabled
by clicking the ON/OFF button.
Note:
Once all the settings are complete click the “Save” button at the bottom right of the web page to
make the settings permanent.
1
2
3
4
5
7
8
9
11
13
12
10
6
Figure 5-11. On/Off Configuration
Transmitter:
1.
TX Block Frequency:
Sets the TX block frequency from 30kHz to 500kHz in 0.125kHz
increments.
2.
TX Reserve Level:
Sets the TX reserve level. The selections are 1W, 3W or 10W.
3.
TX Block Level:
Sets the TX block level. The selections are 1W, 3W or 10W.
4.
Local TX Causes Block:
Check to generate a local block when a block is transmitted to
the far end.
5.
TX Filter Settings:
Click this button to show jumper settings required for allocated
frequency ranges.