73
Section V.
Parameter Function Table
3
Frequency level detection FDT1
output
Refer to P8.19 and P8.20 function codes for details
4
Frequency arrival
Refer to P8.21 function codes for details
5
Null speed operation(stop without
output)
When inverter is in running status and output 0Hz , ON
signal is output.
When inverter is in stop status, OFF signal is output.
6
Motor overload pre-alarm
Judgment will be made according to the prealarm
parameter value before the motor electronic thermal
protection is enabled. If it exceeds the pre-alarm
parameter value, ON signal will be output. Refer to
P9.00 to P9.02 function codes for the descriptions of
motor overload.
7
Inverter overload pre-alarm
When it is found that the inverter is overloaded, ON
signal will be output before the overload protection
occurs.
8
Setup counting value arrived
When the counting value reaches the value of PB.08, it
outputs ON signal.
9
Designated counting value arrived
When the counting value reaches the value of PB.09, it
outputs ON signal.Refers to PB group for details.
10
Length arrived
When the actual length exceeds the setup value in
PB.05, it outputs ON signal.
11
PLC circulation end
When the simple PLC running finishes one circulation, it
outputs a pulse signal with width of 250ms.
12
Total running time arrived
When the accumulated running time of the inverter
exceeds the setup time (P8.17), it outputs ON signal.
13
Frequency limit
When set frequency exceeds upper limit frequency or
lower limit frequency,and inverter output frequency
exceeds upper limit frequency or lower limit frequency,
it outputs ON signal.
14
Torque limit
In speed control mode, if output torque reaches the
torque limit, inverter will be in stall protection status and
output ON signal.
15
RUN ready
When the inverter has no fault and the bus voltage
works normally and the inverter is ready for running, it
outputs ON signal. Upon normal startup, it closes the
output.
16
AI1>AI2
When the voltage value of analog input AI1 is bigger
than that of analog input AI2, it output ON signal.
17
Frequency upper limit arrived
When the running frequency of the inverter reaches the
frequency upper limit, it outputs ON signal.
18
Frequency lower limit arrived
(stop without output)
When the running frequency of the inverter reaches the
frequency lower limit, it outputs ON signal.And output
OFF signal in stop status.
19
Undervoltage state output
When inverter is in undervoltage status, it outpus ON
signal.
20
Communication setup
Please refer to communication protocol.
21
Reserved
Reserved
22
Reserved
Reserved