Section VI.
Fault Diagnosis & Solutions
Fault investigation
1
、
Total power-on time arrive the set value
Fault counter
measures
1
、
Clear record information using parameter initialization function
Fault name
Load off fault
Panel display
Fault No.30= Err30
Fault investigation
1
、
Inverter running current less than P9.64
Fault counter
measures
1
、
Confirm whether load off or P9.64, P9.65parameter settings is
inaccordance with the actual operating condition
Fault name
PID feedback loss during operation fault
Panel display
Fault No.31= Err31
Fault investigation
1
、
PID feedback less than PA.26 set value
Fault counter
measures
1
、
Check PID feedback signal or set PA.26 to a proper value
Fault name
Each wave current limiting fault
Panel display
Fault No.40= Err40
Fault investigation
1
、
Excessive load or motor stall
2
、
Small type selection of inverter.
Fault counter
measures
1
、
Reduce the load and check the motor and mechanical condition
2
、
Choose inverter of greater power level
Fault name
Motor switching fault
Panel display
Fault No.41= Err41
Fault investigation
1
、
Change current motor selection during inverter operation
Fault counter
measures
1
、
Switch the motor after inverter stopped.
Fault name
Excessive speed deviation fautl
Panel display
Fault No.42= Err42
Fault investigation
1
、
Improper set inspection parameters P9.69
、
P9.60
2
、
Wrongly set encoder parameters
3
、
No parameter identification
Fault counter
measures
1
、
Set inspection parameters properly according to actual situation
2
、
Set motor encoder parameters correctly
3
、
Motor parameter identification
Fault name
Motor overspeed fault
Panel display
Fault No.43= Err43
Fault investigation
1
、
No parameter identification
2
、
Wrongly set encoder parameters
3
、
Improper set inspection parameters P9.69
、
P9.60
Fault counter
1
、
Motor parameter identification