Section IV.
Keyboard Operation
25
3.1.2
Peripheral Electric Parts of HV590
PartName
InstallationLocation
FunctionDescription
Circuit breaker
The
front-end
of
theinputcircuit
Disconnect the power supply in case of downstream
equipment is over current
Contactor
Between the circuitbreaker
andthe inverterinputside
Power-onandpower-offoftheinverter.Frequent
power-on/power-off operation(at least once per
minute) on the inverter should be avoided
AC input reactor
Inputsideof the inverter
Improve the power factor of the input side
:
1.Eliminate the high order harmonics of the input
side effectively, and prevent other equipment from
damagingdue to voltage waveform deformation.
2.Eliminate the unbalancedinput current due to
theunbalancedpowerphases.
EMC input filter
Input side ofthe inverter
1.Reduce the external conduction and radiation
interference of the inverter;
2.Reduce the conduction interference flowing from
thepower end to the inverter, thus improving the
anti-interference capacity of the inverter.
3.The common size of 3-phase EMI noise filter is
shown as following
:
confirm the power supply is
3-phase three lines or 3-phase four lines or single
phase. Grounding wire is as short as possible, try
to place the filter near the converter.
Please choose EMI filter when the inverter is used
in residential area, commercial area, science area
as well as situations where higher demand to
prevent radio interference is needed or meeting
CE
、
UL
、
CSA standard but existing equipment that
anti-interference ability is not sufficient.
If needing the filter, please connect with the company.
DC reactor
HV590 series can adopt
external DC reactor
according to the need.
Improve the power factor of the input side
:
1.Improve the overall efficiency and thermal stability
2.Effectively reduce the influence of high order
harmonicsat the input side on the inverter and
reduce the external conduction and radiation
interference.
ACoutput reactor
Between the inverter output
side and the
motor,closetothe inverter
The inverter output side generally has higher
harmonic.When the motor is far from the inverter,
since there are many capacitors in the circuit,
certain harmonics will cause resonance in the circuit
and bring in the following results
:
1.Degrade the motor insulation performance and
damagethe motor for the long run
2.Generatelarge leakage current and cause frequent