Section V.
Parameter Function Table
5.3
Parameters for motor 1
:
P1.00-P1.37
Code
Description/Display
Setting Range
Factory
Setting
Change
Limit
P1.00
Motor type selection
General asynchronous motor
0
0
★
Variable frequency asynchronous motor
1
P1.01
Rated power
0.1kW~1000.0kW
-
★
P1.02
Rated voltage
1V~2000V
-
★
P1.03
Rated current
0.01A~655.35A(Inverter power
≦
55kW)
0.1A~6553.5A(Inverter power >55kW)
-
★
P1.04
Rated frequency
0.01Hz~maximum frequency
-
★
P1.05
Rated revolving speed
1rpm~65535rpm
-
★
Function codes above are motor nameplate parameters. No matter VF control or vector control is the
choosen mode, users should accurately set the relating parameter according to the motor nameplate.
For better VF or vector control performance, users should tune the motor parameter. The accuracy of
the regulation results has intimate relationship with the accuracy of set motor nameplate parameters.
P1.06
Asynchronous motor stator
resistance
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
-
★
P1.07
Asynchronous motor rotor
resistance
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
-
★
P1.08
Asynchronous motor
leakage inductance
0.01mH~655.35mH(Inverter power <=55kW)
0.001mH~65.535mH(Inverter power >55kW)
-
★
P1.09
Asynchronous motor mutual
inductance
0.1mH~6553.5mH(Inverter power <=55kW)
0.01mH~655.35mH(Inverter power >55kW)
-
★
P1.10
Asynchronous motor no
load current
0.01A~P1.03(Inverter power <=55kW)
0.1A~P1.03(Inverter power >55kW)
-
★
P1.06~P1.10 are parameters for asynchronous motor.Generally, motor nameplate do
sen’t contain
such parameters, users can get them throung inverter auto tuning. Among them, 3 parameters
(P1.06~
P1.08) can be get through “ asynchronous motor static tuning”, while all the 5 parameters as well
as encoder phase ,current loop PI etc can be get through“asynchronous motor complete tuning”. When
change the motor rated power (P1.01) or motor rated voltage (P1.02), inverter would automatically
modify the P1.06~P1.10 parameter value and restore them to common standard of Y series motor
parameter.
If the asynchronous motor is unable to be tuned, users could input above parameters with factory
offeredmotor value.
P1.27
Encoder pulses number
1~65535
2500
★
To set ABZ or UVW incremental encoder pulse number per revolution.
In the speed sensor vector control mode, P1.27 must be set accurately.Or motor would not normally
operate.
P1.28
Encoder type
ABZ incremental encoder
0
0
★
UVW incremental encoder
1
Rotary transformer
2
Sine/cosine encoder
3