67
Section V.
Parameter Function Table
Terminal
Set value
Description
DI1
1
Forward(FWD)
DI2
2
Reverse(REV)
DI3
3
Three-line running control
When in the need of running, users should first connect DI3 terminal. Forward and reverse running is
realized through the rising edge of Di1 or DI2
Direction as first control priority control
,
when DI1 is valid
,
DI2 pulse rising edge is invalid,when DI2 is
valid
,
DI1 pulse rising edge is invalid,When in the need of stop, user should disconnect DI3 terminal to
meet the need. Among them, DI
1、
DI
2、
DIn are multi-function input terminal of DI1~DI10. DI
1
,DI
2
are of
pulse valid, while DI3 level valid.
0 invalid. 1 valid. X arbitrarily
SB1
SB2
SB3
Command
0
X
X
Stop
1
1
0
Forward(FWD)
1
0
1
Reverse(REV)
1
1
0->1
Forward(FWD)
1
0->1
1
Reverse(REV)
Fig. 5-8 Three-line control mode 1
Among them
:
SB1
:
Stop button
SB2
:
Forward rotation button
SB3
:
Reverse rotation button
P4.12
Terminal UP/DOWN variation
rate
0.01Hz/s~65.535Hz/s
1.00Hz/s
☆
It is used to set the frequency variation rate (frequency variation per second) when adjusting the set
frequency with terminals UP/DOWN.
When P0.22 (frequency decimal point) is set to 2, range of P4.12 value is 0.001Hz/s~65.535Hz/s.
When P0.22 (frequency decimal point) is set to 1, range of P4.12 value is 0.01Hz/s~655.35Hz/ s.
P4.13
AI curve 1 minimum input
0.00V~P4.15
0.00V
☆
P4.14
AI curve 1 minimum input
corresponding setup
-100.00%~100.0%
0.0%
☆
P4.15
AI curve 1 maximum input
P4.13~10.00V
10.00V
☆
HV590
DIy (REV)
COM
DIx (FWD)
DIn 3-line running control
SB2
SB1
SB3