Section V.
Parameter Function Table
AC.05
AI2 display voltage 1
0.500V~4.000V
Factory
calibration
☆
AC.06
AI2 measured voltage 2
6.000V~9.999V
Factory
calibration
☆
AC.07
AI2 display voltage 2
6.000V~9.999V
Factory
calibration
☆
AC.08
AI3 measured voltage 1
-9.999V~10.000V
Factory
calibration
☆
AC.09
AI3 display voltage 1
-9.999V~10.000V
Factory
calibration
☆
AC.10
AI3 measured voltage 2
-9.999V~10.000V
Factory
calibration
☆
AC.11
AI3 display voltage 2
-9.999V~10.000V
Factory
calibration
☆
This group of function codes are used for calibration of analog input AI , which could eliminate AI
input bias and gain influence. Generally , there is no need of calibration in application, for it has been
calibrated in factory. When restoring the factory value, the parameter would be restored to the default
value of factory calibration.
Measured voltage refers to the actual voltage that has been measured through measuring
instrument such as multimeter. Display voltage refers to the display value that has been sampled by the
inverter. See U0 group (U0.21
、
U0.22
、
U0.23) display.
During calibration, put the multimeter measurement value and the U0 value respectively into the
function codes above, inverter would automatically calibrate the AI zero off and gain.
AC.12
A01 target voltage 1
0.500V~4.000V
Factory
calibration
☆
AC.13
A01 measured voltage 1
0.500V~4.000V
Factory
calibration
☆
AC.14
A01 target voltage 2
6.000V~9.999V
Factory
calibration
☆
AC.15
A01 measured voltage 2
6.000V~9.999V
Factory
calibration
☆
AC.16
A02 target voltage 1
0.500V~4.000V
Factory
calibration
☆
AC.17
A02 measured voltage 1
0.500V~4.000V
Factory
calibration
☆
AC.18
A02 target voltage 2
6.000V~9.999V
Factory
calibration
☆
AC.19
A02 measured voltage 2
6.000V~9.999V
Factory
calibration
☆
This group of function codes are used for calibration of analog output AO. Generally , there is no
need of calibration in application, for it has been calibrated in factory. When restoring the factory value,
the parameter would be auto restored to the default value of factory calibration.
Target voltage refers to inverter theoretical output voltage, while measured voltage refers to the
actual voltage that has been measured through measuring instrument such as multimeter.