108
Section V.
Parameter Function Table
2
:
Continuous circulation
Upon completion of one single cycle of the inverter, it will enter next cycle and not stop until stop
command is given.
Fig.5-30Simple PLC schematic diagram
PC.17
PLC power off memory
selection
1bit
Power off memory selection
00
☆
Power off without memory
0
Power off with memory
1
10bit
Stop memory selection
Stop without memory
0
Stop with memory
1
PLC power off memory refers to memorizing the PLC running stage and running frequency before
power off, and continues to run from the memory stage upon next power-on. If 1bit is set to 0, PLC process
would restart upon power-on.
PLC stop memory refers to the record of PLC running stage and running frequency of the time before.
Next time PLC continues to run from the memory stage. If 10bit is set to 0, PLC process would restart upon
power-on.
PC.18 PLC 0segment running time
0.0s(h) ~ 6553.5s(h)
0.0s(h)
☆
PC.19 PLC 0segment acc./dec. time
0~3
0
☆
PC.20 PLC 1segment running time
0.0s(h)~6553.5s(h)
0.0s(h)
☆
PC.21 PLC 1segment acc./dec. time
0~3
0
☆
PC.22 PLC 2segment running time
0.0s(h)~6553.5s(h)
0.0s(h)
☆
PC.23 PLC 2segment acc./dec. time
0~3
0
☆
Running direction
PC.19
PC.00
PC.21
PC.01
PC.18
PC.20
PC.23
PC.02
PC.14
PC.15
250ms pulse
t
DO or RELAY output