98
Section V.
Parameter Function Table
PT100
1
PT1000
2
P9.57
Motor overheating protection
threshold
0
℃
~200
℃
110
℃
☆
P9.58
Motor overheating pre-alarm
threshold
0
℃
~200
℃
90
℃
☆
Temperature signal of motor temperature sensor should be connected to multi-function I/O expansion
card(optional). Analog input signal AI3 can be used as motor temperature sensor input. Motor temperature
sensor signal is connected to AI3,PGND end.
AI3 analog input end of HV590 supports PT100&PT1000 motor temperature sensors. Correct sensor
type should be set during operation. Motor temperature value is displayed in U0.34.
When motor temperature exceeding the motor overheating protection threshold (P9.57), inverter would
give fault alarm and processing according to the selected protection action mode.
When motor temperature exceeding the motor overheating pre-alarm threshold(P9.58), inverter multi-
function digital DO would output motor overheating pre-alarm ON signal.
P9.59
Transient stop selection
Invalid
0
0
☆
Deceleration
1
Deceleration to stop
2
P9.60
Transient stop action pause
protection voltage
80.0%~100.0%
90.0%
☆
P9.61
Transient stop voltage
recovery judgment time
0.00s~100.00s
0.50s
☆
P9.62
Transient stop action
judgment voltage
60.0%~100.0%(Standard bus voltage)
80.0%
☆
Содержание HV590 Series
Страница 1: ...HV590 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 189: ......
Страница 192: ......