93
Section V.
Parameter Function Table
P9.11
Fault auto reset interval
0.1s~100.0s
1.0s
☆
The waiting time of the inverter from the fault alarm to auto reset.
P9.12
Input phase lack protection
selection
1bit
Input phase lack protection selection
11
☆
Forbidden
0
Allowed
1
10bit
Contactor attracting protection
Forbidden
0
Allowed
1
1bit
:
It is used to choose whether to protect input phase loss.
10bit
:
Contactor attracting protection
HV590 series inverter above 132kW (type G) has input phase fault protection function.For the inverter
below 132kW (type P), the input phase fault protection function is invalid at any setup.
P9.13
Output phase lack protection
selection
Invalid
0
1
☆
valid
1
It is used to choose whether to protect output open-phase.
P9.14
The first fault type
0~99
-
●
P9.15
The second fault type
0~99
-
●
P9.16
The latest fault type
0~99
-
●
It records the latest 3 fault types for the inverter
:
0 means no fault and 1 to 99 correspond to refer to
Chapter 6 for the details.
Table of fault type
:
No.
Fault display
Fault type
0
Reserved
No fault
1
1=Err01
Reserved
2
2= Err02
Acceleration over current
3
3= Err03
Deceleration over current
4
4=Err04
Constant speed over current
5
5=Err05
Acceleration over voltage
6
6= Err06
Deceleration over voltage
7
7=Err07
Constant speed over voltage
8
8=Err08
Control power supply fault
9
9=Err09
Undervoltage fault
10
10=Err10
Inverter overload
11
11= Err11
Motor overload
12
12= Err12
Input phase lack
13
13= Err13
Output phase lack
14
14= Err14
Module overheating
15
15= Err15
External equipment fault
16
16= Err16
Communication fault
Содержание HV590 Series
Страница 1: ...HV590 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 189: ......
Страница 192: ......