156
Appendix I
H5RS485 Card & RS485Communication Protocol
Read inverter status
:
(read-only)
Status word address
Status word function
3000
0001
:
Forward operation
0002
:
Reverse operation
0003
:
Stop
Parameters lock password check
:
(if the return is the 8888H, it indicates the password
checksum pass)
Password address
Contents of input password
1F00
*****
Digital output terminal control
:
(write-only)
Command address
Command content
2001
BIT0
:
DO1 Output control
BIT1
:
DO2 Output control
BIT2 RELAY1 Output control
BIT3
:
RELAY2 Output control
BIT4
:
Y1R Output control
BIT5
:
VY1
BIT6
:
VY2
BIT7
:
VY3
BIT8
:
VY4
BIT9
:
VY5
Analog output AO1 control
:
(write-only)
Command address
Command content
2002
0~7FFF indicates 0
%
~100
%
Analog output AO2control
:
(write-only)
Command address
Command content
2003
0~7FFFindicates 0
%
~100
%
(PULSE)output control
:
(write-only)
Command address
Command content
2004
0~7FFFindicates 0
%
~100
%
Inverter fault description
:
Inverter fault address
Inverter fault information
8000
0000
:
No fault
0001
:
Reserved
0002
:
Speed-up over current
0003
:
Speed-down over current
Содержание HV590 Series
Страница 1: ...HV590 Series Frequency Inverter User Manual HNC Electric Limited ...
Страница 189: ......
Страница 192: ......