89
Section V.
Parameter Function Table
P8.36
Output current overlimit value
0.0%(No detection)
0.1%~300.0%(Motor rated current)
200.0%
☆
P8.37
Output current overlimit
detection delay time
0.00s~600.00s
0.00s
☆
Fig.5-22 Output current overlimit detection schematic diagram
When inverter output current is larger than output current overlimit value(P8.36) ,and lasting time
exceeds the software overlimit detection delay time ,inverter multi-function terminal DO output ON signal,
fig.5-22 is schematic diagram of output current overlimit detection.
P8.38
Random currentarrival 1
0.0%~300.0%(Motor rated current)
100.0%
☆
P8.39 Random current arrival range1 0.0%~300.0%(Motor rated current)
0.0%
☆
P8.40 Random currentarrival 2
0.0%~300.0%(Motor rated current)
100.0%
☆
P8.41 Random currentarrival range2
0.0%~300.0%(Motor rated current)
0.0%
☆
When inverter output current is within the positive & negative detection range of random arrival current
value , multi-funtion terminal DO output ON signal.
HV590 offers two groups of random current arrival range detection parameters ,as shown in fig. 5-23.
Output current
Output current overlimit
detection signal
t
t
P8.36
ON
P8.37