94
Section V.
Parameter Function Table
17
17=Err17
Contactor fault
18
18= Err18
Current inspection fault
19
19= Err19
Motor tuning fault
20
20= Err20
Encoder /PG card fault
21
21= Err21
EEPROM read & write fault
22
22= Err22
Inverter hardware fault
23
23= Err23
Short circuit to ground fault
24
Reserved
Reserved
25
Reserved
Reserved
26
26= Err26
Total running time arrival fault
27
27= Err27
User-defined fault 1
28
28=Err28
User-defined fault 2
29
29=Err29
Total power-on time arrival fault
30
30= Err30
Load off fault
31
31= Err31
PID feedback loss during operation fault
40
40= Err40
Each wave current limiting fault
41
41=Err41
Motor switching fault
42
42= Err42
Excessive speed deviation fault
43
43= Err43
Motor overspeed fault
45
45=Err45
Motor overtemperature fault
51
51= Err51
Initial position fault
P9.17
Third fault frequency
The latest fault frequency
●
P9.18
Third fault current
The latest fault current
●
P9.19
Third fault bus voltage
The latest fault bus voltage
●
P9.20
Third fault input terminal
The latest fault digital input terminal status, order as below
:
When in
put terminal status is ON, it’s corresponding
binary digit is 1. OFF corresponds to 0. All DI status are
converted to decimal display.
●
P9.21
Third fault output terminal
The latest fault digital output terminal status, order as
below
:
When out
put terminal status is ON, it’s corresponding
binary digit is 1. OFF corresponds to 0. All status are
converted to decimal display.
●
BIT9
BIT8
BIT7
BIT6
BIT5
BIT4
BIT3
BIT2
BIT1
BIT0
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DI9
DI0
BIT4
BIT3
BIT2
BIT1
BIT0
FMP
REL1
REL2
DO1
DO2