50
Section V.
Parameter Function Table
Communication setup
9
10bit
Terminal command bound frequency
source selection
Without bound
0
Digital setup frequency source
1
AI1
2
AI2
3
AI3(Potentiometer)
4
PULSE pulse setup(DI5)
5
MS command
6
Simple PLC
7
PID
8
Communication setup
9
100bit
Communication command binding
frequency source selection
Without bound
0
Digital setup frequency source
1
AI1
2
AI2
3
AI3(Potentiometer)
4
PULSE pulse setup(DI5)
5
MS command
6
Simple PLC
7
PID
8
Communication setup
9
It defines bound combination between 3 running command channels and 9 frequency setup
channels, which is easy to achieve synchronous switching.
Frequency setup
channels above have the same definition with P0.03 “main frequency source X
selection”, please refer to P0.03 for details. Different running command channels can bind the same
frequency setup channel. When the command source is valid during command source & frequency
source binding, set frequency source of P0.03~P0.07 is invalid.
P0.28
Communication expansion
card
Modbus communication card
0
0
☆
Profibus.DP communication card
1
CANopen communication card
2
CANlink communication card
3
HV590 series offers 3 kinds of communication mode. All of the 3 need to be equipped with optional
communication card .And they can not be used at the same time.
P0.28 is used to set the type of the optional communication card. When user replace the
communication card , P0.28 should be properly set.