Supervisormode
WTX110
A4774-1.0
HBM: public
137
Meaning of parameter P1
A correction factor of 1 means that the difference between the actual weight
and target weight (either too much or not enough material added) will be
included in the next cut-off point at a rate of 100%. With a correction factor of
0.5, only 50% of the difference is included in the calculation.
10.2.9
Re-dosing
(Re-Dosing
)
If the previously measured actual value is below the lower tolerance limit,
re-dosing is carried out. When optimization is active (parameter P1 > 0), the
result of a re-dosing operation does not change the cut-off points.
Re-dosing occurs with fine flow.
Menu
Key
Function/Secondary selection
Re-dosing
Off
Re-dosing turned off
1
Re-dose if fine flow cut-off point < current
measured value < lower tolerance limit
When to re-dose?
At the start of the batching process
2
Re-dose if previously measured actual weight
< lower tolerance limit
When to re-dose
After checkweighing
3
Re-dose if
fine flow cut-off point < current measured
value < lower tolerance limit
When to re-dose?
At the start of the batching process
OR
Re-dose if previously measured actual weight
< lower tolerance limit
When to re-dose?
After checkweighing
Содержание WTX110
Страница 1: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 3: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 10: ...8 A4774 1 0 HBM public WTX110 17 Geo values 212...
Страница 55: ...Installation WTX110 A4774 1 0 HBM public 53 Fig 4 12 Positioning of ALI option on the WTX110 motherboard...
Страница 217: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 224: ...8 A4774 1 0 HBM public WTX110 17 Geowerte 217...
Страница 259: ...Installation WTX110 A4774 1 0 HBM public 43 Abb 4 6 Positionierung DIO Modul SIO auf der WTX110 Hauptplatine...
Страница 271: ...Installation WTX110 A4774 1 0 HBM public 55 Abb 4 12 Positionierung Alibi Speicher auf WTX110 Hauptplatine...