Calibration
178
A4774-1.0
HBM: public
WTX110
11.8
Adaptation
For more information on the keys necessary to access this menu group, go to
the
.
Menu
Key
Function/Secondary selection
Select group 1-9
Press 5 x for group
5 Adaptation
Motion Window
0.5D
Motion window
Here the window is set in digits (increments),
which must contain consecutive weight values for
the A/D converter to signal a stationary weight
value.
OFF
Motion control off
3.0D, 2.0D, 1.0D, 0.5D
Window size
MotionCounter
99
Time span for standstill recognition
Here the time span is set in which consecutive
weight values must occur in the motion window
for standstill to be detected. 1 unit = 0.02 sec.
Example: 20 = 0.4 sec
Filter Size
OFF
Filtration level
The filtration level of the digital filter can be set
here. The following settings are possible:
Off
0
1
to
20
Light to heavy filtering.
With a very unstable scale display (such as in the
case of live cattle weighers) heavy filtering is
recommended.
Содержание WTX110
Страница 1: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 3: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 10: ...8 A4774 1 0 HBM public WTX110 17 Geo values 212...
Страница 55: ...Installation WTX110 A4774 1 0 HBM public 53 Fig 4 12 Positioning of ALI option on the WTX110 motherboard...
Страница 217: ...Operating Manual Bedienungsanleitung English Deutsch WTX110...
Страница 224: ...8 A4774 1 0 HBM public WTX110 17 Geowerte 217...
Страница 259: ...Installation WTX110 A4774 1 0 HBM public 43 Abb 4 6 Positionierung DIO Modul SIO auf der WTX110 Hauptplatine...
Страница 271: ...Installation WTX110 A4774 1 0 HBM public 55 Abb 4 12 Positionierung Alibi Speicher auf WTX110 Hauptplatine...