82
ADP200 • Quick installation guide - Specifications and connection
Index
Error message shown on
the display [on the inte-
grated keypad]
Sub-code
Description
11
Load def plc
Condition:
may occur during loading of the parameter database saved in the Flash of the Mdplc application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message appears the drive restores the default database, i.e. the one that was downloaded.
[LDPL]
0001H-1
The database saved is not valid
Solution:
Set the parameters to the value required and perform
Save parameter
12
Plc cfg error
Condition:
may occur during loading of the Mdplc application
The Mdplc application present on the drive is not run.
[PLCE]
0004H-4
The application downloaded has a different Crc on DataBlock and Function table
0065H-101
The application downloaded has an invalid identifier (Info)
0066H-102
The application downloaded has an incorrect task number (Info)
0067H-103
The application downloaded has an incorrect software configuration
0068H-104
The application downloaded has a different Crc on DataBlock and Function table
0069H-105
A Trap error or System error has occurred.
The drive automatically performs a Power-up operation.
The application is not run.
See in Alarm List for further information regarding the error occurred
006AH-106
The application downloaded has an incorrect identifier (Task)
006BH-107
The application downloaded has an incorrect task number (Task)
006CH-108
The application downloaded has an incorrect Crc ( Code)
Solution:
Remove the Mdplc application or download a correct Mdplc application
13
Plc 1 [PLC1]
14
Plc 2 [PLC2]
Reserved messages and dedicated to the PLC application. See the application manual.
15
Plc 3 [PLC3]
16
Plc 4 [PLC4]
17
Opt bus fault
Condition:
this may occur when the drive is turned on, during fieldbus card setup. Error during configuration or communication error.
[OPTB]
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is 0, the error regards a communication problem.
XXX0H-X
If the first digit to the left of "H" in the alarm sub-code is other than 0, the error regards a configuration problem.
Solution:
For configuration errors, check the configuration of the bus communication, type of bus, baudrate, address, parameter setting
For communication errors, check wiring, termination resistors, disturbance immunity, timeout settings.
For further details, please refer to the user guide for the specific bus.
18
Wrong key
Condition
: this may occur when powering the drive, if the incorrect enable key is inserted for a given firmware function.
[KEYF]
0001H-1
Incorrect PLC key. PLC application not available.
Solution
: Ask Gefran to supply the correct key to enable the desired firmware function.
19
Key expiring
Condition:
this may occur at drive power-on if the incorrect enabling key was inserted for a given firmware function. At this stage the firmware function
can still be used freely, but this time limit is about to expire
[KEYE]
XXXXH-X
Number of hours for which the function can still be used freely.
Solution:
Ask Gefran for the correct key to enable the desired firmware function.
20
Parameter error
Condition:
An error occurs during the enabling of the parameter database saved in flash; one parameter value is out of range.
[PE]
XXX0H-X
Code 0001H-1 indicates that one or more parameter have value out of range.
Solution: Press the esc key and go inside Alarm log. Inside alarm Log there is Param error with a hex code of IPA parameter causing the error.
Set the parameter that has caused the error to the correct value within the range and run
Save parameters
. Switch the drive off and then switch it back
on again. If the IPA of the parameter is not shown in the manual, contact the service centre.
21
Encoder error
Condition:
this condition may occur when the drive is powered during encoder setup each time parameter 552
Regulation mode
is set.
[ENCE]
100H-256
Cause
: An error occurred during setup; the information received from the encoder is not reliable. If the encoder is used for feedback the
Speed fbk loss
alarm is also generated.
Solution:
Take the recommended action for the
Speed fbk loss
alarm.
200H-512
Cause
: The firmware on the optional encoder card is incompatible with that on the regulation card. The information received from the
encoder is not reliable
Solution:
Contact Gefran in order to update the firmware on the optional encoder card.
22
Options cfg changed
Condition
: this may occur when powering the drive if an expansion card has been removed or replaced or the incorrect enable key is inserted for a given
firmware function.
[OCFG]
0064H-100
Card removed from slot 1
0014H-20
Card removed from slot 2
0078H-120
Card removed from slot 1 and from slot 2
Solution
: Check the hardware configuration, then press ESC. Save the parameters (
Save parameters
, menu 04.01 par 550) to save the new hardware
configuration.
23
Autotune
(phasing)
0
No error
[SLFP]
1
The commands are not configured in Local mode.
Solution:
Execute the requested configuration
2
The
Commands local sel
parameter has not been configured from the keypad
Solution:
Execute the requested configuration
3
The motor plate data parameters have changed but the
Take parameters
command, PAR 2020, has not been executed
Solution:
Execute the
Take parameters
command.
4
The motor is not connected
Solution:
Connect the motor