44
ADP200 • Quick installation guide - Specifications and connection
7.6 Optional Keypad interface (keypad connector)
Keypad
(XS1)
connector
1
5
6
9
Several devices can be connected to the multifunction keypad connector (9-pin D-SUB female receptacle connector
XS1) and are automatically recognised and managed.
- The keypad is supplied with a 40 cm-long cable, for longer distances, a 1:1 non-crossover cable must be used (9
shielded cables, e.g. code 8S8F59, length 5 m).
- Very long cables (max. 15 m) must be of good quality with low voltage loss (max. 0.3 ohm/m).
The connections have no galvanic isolation!
7.7 Saving data on the Memory Card
With the ADP200 drive, data can be saved on a normal Secure Digital-type memory card. In order to use the memory
card, the specific adapter (SD-ADL) must be connected by inserting it into the dedicated slot on the front of the drive.
For further information, see chapter 8.9.
SD Card
ADP200
Caution