42
ADP200 • Quick installation guide - Specifications and connection
A) Connection of an industrial PC with RS485
The following are required for connection:
• shielded cable for the
RS485 / RS485
connection (see figure 7.5.2), code 8S864C.
B)
Connection to a PC with RS232 port and OPT-RS485-ADP
option (isolated, for point to point and multidrop)
The following are required for connection:
• optional
OPT-RS485-ADP
card (for galvanic isolation), code S5L85
• an optional
PCI-COM
adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the RS232 connector of the PC,
see figure 7.5.2.
C)
Connection to a PC with RS232 port (not isolated)
The following are required for connection:
• an optional
PCI-COM
adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the RS232 connector of the PC,
see figure 7.5.2.
D) Connection to a PC with USB port (not isolated)
The following are required for connection:
• an optional
USB/RS232
adapter, code 8S8F62 (including the cable for USB connection)
• an optional
PCI-COM
adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the USB/RS232 adapter, see
figure 7.5.2.
7.4.2 Drive / RS485 port point-to-point connection (isolated)
To make the connection with galvanic isolation, the
OPT-RS485-
ADP
optional card is required.
The card is equipped with a 9-pin D-SUB male receptacle connector which must be inserted in the
RS485
connector of
the ADP200 drive.
Connect
P1
side to RS485 connector of ADP200, and
J1
side to the PC serial line, the adapters indicated in paragraph
7.4.1 must be used.
OPT-RS485-ADP (cod. S5L85)
J1 Pin
Description
S1
9-pin D-
SUB Female,
to serial cable
P1
J1
ON
OFF
9-pin D-
SUB Male,
ADP side
1
N.C.
To insert termination switch
set S1-1/2 to ON
2
N.C.
3
A
4
EQP
5
Reserved
6
Reserved
7
B
8
N.C.
9
N.C.
Figure 7.5.3: OPT-RS485-ADP card
7.4.3 RS 485 multi-drop connection
For the multi-drop connection, the
OPT-RS485-
ADP
optional card must be installed on each drive; the ends of the con-
nection must have
S1
termination switch set to ON. The multi-drop connection is always galvanically insulated.
Up to 20 drives can be connected; the maximum length of the connection is 200 meters.
ADP200
ADP200
ADP200
OPT-RS485-ADP
3
3
3
7
7
7
4
4
4
EQP
B
A
S1=ON
S1=OFF
S1=ON
OPT-RS485-ADP
OPT-RS485-ADP
Industrial PC,
PLC,
etc..
(with RS485)
ADP200
ADP200
ADP200
3
3
3
7
7
7
RS485
4
4
4
EQP
B
A
S1=OFF
S1=OFF
S1=ON
OPT-RS485-ADP
OPT-RS485-ADP
OPT-RS485-ADP
Termination=ON
Industrial PC,
PLC,
etc..
(with RS485)
Termination=OFF
RS485