ADP200 • Quick installation guide - Specifications and connection
10.3 Messages
Note !
For more information see
chapter 8.7
.
Index
Error message shown on
the display [on the inte-
grated keypad]
Sub-code
Description
1
Load default param [LDEF]
Condition:
may occur during loading of the parameter database saved in flash normally appears in the following conditions: at initial power-on when a
new firmware version is downloaded, when the regulation is installed on a new size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message is displayed, the drive automatically performs the
Load default
command.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution:
Set the parameters to the value required and perform
Save parameter
2
3
4
Option detect slot 1 [OPT1]
Option detect slot 2 [OPT2]
Option detect slot 3 [OPT3]
Condition:
when the drive is turned on it recognises the presence of an optional card. One of the messages is shown on the display for a few seconds
0H-0
None
0004H-4
CAN
0008H-8
Enc 1 (EXP-DE-I1R1F2-ADL)
0108H-264
Enc 2 (EXP-SE-I1R1F2-ADL)
0208H-520
Enc 3 (EXP-SESC- I1R1F2-ADL)
0308H-776
Enc 4 (EXP-EN/SSI- I1R1F2-ADL)
0408H-1032
Enc 5 (EXP-HIP- I1R1F2-ADL)
0508H-1288
Enc 6 (EXP-RES-I1-ADP/ EXP-RES-I1R1-ADP)
0101H-257
I/O 1 (EXP-IO-D4-ADL)
0501H-1281
I/O 2 (EXP-IO-D8R4-ADL)
0901H-2305
I/O 3 (EXP-IO-D16R4-ADL)
0F01H-3841
I/O 4 (EXP-IO-D12A2R4-ADL)
1301H-4865
I/O 5 (EXP-IO-D8A4R4-ADL)
1501H-5377
I/O 6 (EXP-IO-D5R3-F-ADL)
1F01H-7937
I/O 7 (EXP-IO-D10A3R2-ADP)
2301H-8961
I/O 8 (EXP-IO-D8A4R2-ADP)
00FFH-255
Unknown
Solution:
5
Autotune (motor)
Condition:
this may occur during the Autotune procedure
[SLFT]
0
No error
1
The commands are not configured in Local mode.
Solution:
Execute the requested configuration
2
The
Commands local sel
parameter has not been configured from the keypad
Solution:
Execute the requested configuration
3
The motor plate data parameters have changed but the
Take parameters
command, PAR 2020, has not been executed
Solution:
Execute the
Take parameters
command.
4
The motor is not connected
Solution:
Connect the motor
5
While running self-tuning the ESC key was pressed or the enable contact was opened or an alarm occurred. The Autotune command
was sent with the drive in the alarm condition
Solution:
Eliminate the reason for the alarm, remove the reason for the opening of the enable contact, reset alarms.
6
A setting performed by the Autotune function produced a parameter value outside the min or max range.
Solution:
Check the motor plate data or drive and motor sizes have been combined incorrectly.
7
The Autotune command was sent without being enabled.
Solution:
Close the enable contact before sending the Autotune command
8
Internal calculation error concerning IGBT control
Solution
: Perform autotuning once more, if the problem persists, contact the Gefran technical support centre.
9
The drive has measured a stator resistance value exceeding the set limit.
Solution
: contact the Gefran technical support centre.
10
The drive has measured a stator resistance value below the set limit.
Solution
: contact the Gefran technical support centre.
11-12
Measurement of DTL internal compensation voltage outside accepted range.
Solution
: check connection between drive and motor.
If correct, the drive is faulty, contact the Gefran technical support centre.