ADP200 • Quick installation guide - Specifications and connection
Step 1 - Electrical connections
Make the connections as described in paragraph 7.3.2.
Checks to be performed before powering the drive
•
Check that the supply voltage is correct and that the input terminals on the drive (L1, L2 and L3) are connected
correctly.
•
Check that the output terminals on the drive (U, V and W) are connected to the motor correctly.
•
Check that all the drive control circuit terminals are connected correctly. Check that all control inputs are open.
•
Check the encoder connections, see section A.3 of the Appendix.
Powering the drive
•
After completing all the checks described above, power the drive and proceed to step 2.
Step 2 - Setting motor parameters
Note!
Def:
The factory (default) setting depends on the size of the drive that is connected. These values refer to the ADP200-2110-...
03 STARTUP WIZARD
Set motor data?
E=Yes
Down=Next
E
SEQ
SEQ . 01
PAR: 2000
Rated voltage
175
V
Def:
400
E
SEQ
SEQ . 01
PAR: 2000
Rated voltage
00000017
5
v
Def:
400
▲
176 V
▼
174 V
E
SEQ
SEQ . 02
PAR: 2002
Rated current
9.6
A
Def:
19.4
E
SEQ
SEQ . 02
PAR: 2002
Rated current
00000009.
6
A
Def:
19.4
▲
9.7 A
▼
9.5 A
E
SEQ
SEQ . 03
PAR: 2004
Rated speed
3000
rpm
Def:
3000
E
SEQ
SEQ . 03
PAR: 2004
Rated speed
000000300
0
rpm
Def:
3000
▲
3001 rpm
▼
2999 rpm
E
SEQ
SEQ . 04
PAR: 2008
Pole pairs
4
Def:
4
E
SEQ
SEQ . 04
PAR: 2008
Pole pairs
000000000
4
Def:
4
▲
5
▼
3
E
SEQ
SEQ . 05
PAR: 2010
Torque constant
1.29
Nm/A
Def:
1.55
E
SEQ
SEQ . 05
PAR: 2010
Torque constant
000001.2
9
Nm/A
Def:
1.55
▲
1.30Nm/A
▼
1.28Nm/A
E
SEQ
SEQ . 06
PAR: 2012
EMF constant
0.74
Wb
Def: 0.89
E
SEQ
SEQ . 06
PAR: 2012
EMF constant
000000.7
4
Wb
Def: 0.89
▲
0.75 Wb
▼
0.73 Wb
E
Set the plate data of the motor connected, following the instructions given on the previous pages.
Rated voltage [V]:
the rated voltage of the motor indicated on the data plate.
Rated current [A]:
motor rated current; approximately, the value should not be less than 0.3 times the rated current of the drive, output current
class 1 @ 400 V on the data plate of the drive.
Rated speed [rpm]:
motor rated speed; see data plate.
Pole pairs:
Number of motor pole pairs; see data plate.
Torque constant (KT):
(KT) Ratio between the torque generated by the motor and the current required to supply it.
EMF constant:
(KE = KT / √3) Electromotive force constant, which represents the ratio between motor voltage and motor rated speed.
Note!
When data entry is complete the
Take parameters
command is executed automatically (menu 16 MOTOR DATA, PAR: 2020). The motor data entered during
the STARTUP WIZARD procedure are saved in a RAM memory to enable the drive to perform the necessary calculations.
These data are lost if the device is switched off. To save the motor data follow the procedure described in step 9.
At the end of the procedure proceed to step 3