4.4 Input electrical data
Connection to TT and TN networks ���������� yes
Choke ������������������������������� Sizes 2...3: Optional (AC side), sizes 4-5 : integrated (DC side)
Size
Input
voltage
U
ln
Input
frequency
THD %
Overvoltage
threshold
(Vdc)
Undervoltage
threshold
(Vdc)
I
n
AC input current for continuous operation
DC-Link
Capacity
@ 230 Vac
(Arms)
@ 400 Vac
(Arms)
@ 480 Vac
(Arms)
(Vac)
(Hz)
@230V
@400V
@480V
Without
input
choke
With
input
choke
Without
input
choke
With
input
choke
Without
input
choke
With
input
choke
(µF)
2075
three-phase
230-400-
480Vac
-15%+10%
50/60 Hz,
± 5%
< 75
(1)
< 40
(2)
< 75
(1)
< 50
(2)
< 70
(1)
< 60
(2)
820 Vdc
@ 480 Vac = 470 Vdc
@ 460 Vac = 450 Vdc
@ 400 Vac = 391 Vdc
@ 230 Vac = 225 Vdc
24
20
24
20
21
19
680
2110
< 75
(1)
< 40
(2)
28
24
28
25
25
24
1020
3150
< 75
(1)
< 40
(2)
40
34
40
35
35
33
1500
3185
< 75
(1)
< 40
(2)
48
42
48
44
43
41
2250
3220
< 75
(1)
< 40
(2)
51
45
51
47
46
44
2700
4300
(3)
< 40
(1)
< 45
(1)
< 55
(1)
64
-
65
-
61
-
2350
4370
(3)
< 40
(1)
79
-
80
-
75
-
2350
4450
(3)
< 40
(1)
96
-
99
-
93
-
2800
5550
(3)
< 40
(1)
112
-
116
-
109
-
4700
5750
(3)
< 40
(1)
158
-
161
-
148
-
5600
5S550
(4)
< 40
(1)
< 55
(1)
< 65
(1)
-
113
-
120
-
114
4700
5S750
(4)
< 40
(1)
< 45
(1)
< 55
(1)
-
158
-
161
-
148
5600
(1) @ rated Iout without AC input chokes.
(2) with LR3 AC input chokes.
(3) with integrated DC input choke, in accordance with EN 61800-3.
(4) ADP200-5S550 and 5S750 models: AC input external choke is mandatory.
4.5 Output electrical data
Motor type ��������������������������� Synchronous
Maximum output voltage U2 �������������� 0.98 x U
ln
(U
ln
= AC input voltage)
Maximum output frequency f2 ������������� 300 Hz
Size
I
n
Rated output current
(
f
sw
= default)
P
n
mot
(Recommended motor power,
f
sw
= default)
f
sw
(4)
Switching
frequency
Reduction
factor
IGBT
braking unit
@U
ln
=
230V
ac
@U
ln
=
400V
ac
@U
ln
=
460V
ac
@U
ln
=
230V
ac
@U
ln
=
230V
ac
@U
ln
=
400V
ac
@U
ln
=
460V
ac
Other
Default
K
t
K
alt
K
v
(A)
(A)
(A)
(kW)
(Hp)
(kW)
(Hp)
(kHz)
(kHz)
(1)
(2)
(3)
2075
18.5
18.5
16.7
4
5
7.5
10
8
4
0.9
1.2
0.9
Standard internal (with
external resistor);
braking torque 150%
MAX
External optional on
5750 size.
2110
22
22
19.8
5.5
7.5
11
15
8
4
0.9
1.2
0.9
3150
32
32
28.8
7.5
10
15
20
8
4
0.9
1.2
0.9
3185
39
39
35.1
9
15
18.5
25
8
4
0.9
1.2
0.9
3220
42
42
37.8
11
15
22
30
8
4
0.9
1.2
0.9
4300
60
60
54
15
20
30
40
8
4
0.9
1.2
0.9
4370
75
75
67.5
18.5
25
37
50
8
4
0.9
1.2
0.9
4450
90
90
81
22.0
30
45
60
8
4
0.9
1.2
0.9
5550 / 5S550
105
105
94
30
40
55
75
8
4
0.9
1.2
0.9
5750 - 5S750
150
150
135
37
50
75
100
8
4
0.9
1.2
0.9
The derating factors shown in the table are applied to the rated DC output by the user. They are not automatically
implemented by the drive: Idrive = In x Kalt x Kt x Kv
(1) K
t
: Derating factor for ambient temperature of 50°C (1% every °C above 40°C)
(2) K
alt
: Derating factor for installation at altitudes above 1000 meters a.s.l. Value to be applied = 1.2% each 100 m increase above 1000 m (up to a maximum of 2000 m).
E.g.: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; I
n
derated = (100 - 12) % = 88 % I
n
(3) Kv : Derating factor for mains voltage at 460/480Vac.
(4) There is also the possibility to set a variable switching frequency through parameter setting.