ADP200 • Quick installation guide - Specifications and connection
33
7.1.7 Connection of AC and DC chokes
Size
AC-Choke
DC-Choke
2075
Optional (*)
(*) Mandatory if Pcc line exceeds the values on chapter
Optional
2110
3150
3185
3220
4300
Optional
Integrated
4370
4450
5550
5750
5S550
Mandatory
Not integrated and not connectable (no terminals)
5S750
The drive can use both a three-phase choke on the AC power line and, for 7.5 to 22 kW drives only, a DC choke be-
tween terminals C1 and C.
Refer to
chapter 5.2
for the recommended chokes.
If no DC choke is used, terminals C1 and C must be bridged (sizes 2 and 3).
7.1.7.1 Connection of AC choke
ADP200-2075...3220
ADP200-4300...5550
L1 L2 L3 BR C1 C
D
U
V
W
K1M
L1
L2
L3
F1
(
400-
50/60 Hz)
3ph, 230-
480 V
AC
,
AC chokes
(optional)
L1 L2 L3 BR1
C
D
U
V
W
BR2
K1M
L1
L2
L3
F1
(
400-
50/60 Hz)
3ph, 230-
480 V
AC
,
AC chokes
(optional)
ADP200-5750
ADP200-5S550 - ADP200-5S750
L1 L2 L3 C
D
U
V
W
K1M
L1
L2
L3
F1
(
400-
50/60 Hz)
3ph, 230-
480 V
AC
,
AC chokes
(optional)
K1M
L1 L2 L3
F1
(3ph, 230-400-480 V
AC
,
50/60 Hz)
AC chokes
(optional)
7.1.7.2 Connection of DC choke
ADP200-2075...3220
L1 L2 L3 BR C1 C
D
U
V
W
K1M
L1
L2
L3
F1
(
400-
50/60 Hz)
3ph, 230-
480 V
AC
,
DC choke
(optional)
Attention