EMR-5000
IM02602012E
www.eaton.com
966
t-multiplier
x * Pickup
(Multiples of Pickup)
Trip
Reset
t =
0.14
*t-multiplier [s]
Pickup
-1
I
( )
2
t =
0.14
*t-multiplier [s]
Pickup
-1
I
( )
0.02
t [s]
Notice!
Various Reset Modes are available . Resetting via characteristic, delayed, and
instantaneous .
IEC NINV