EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Current8
Interrupted Current Level #8
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
16.00kA
[Control
/Bkr
/Bwear]
Count8
Open Counts Allowed #8
Only available if:Bwear Curve Fc = Active
1 - 32000
75
[Control
/Bkr
/Bwear]
Current9
Interrupted Current Level #9
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
20.00kA
[Control
/Bkr
/Bwear]
Count9
Open Counts Allowed #9
Only available if:Bwear Curve Fc = Active
1 - 32000
45
[Control
/Bkr
/Bwear]
Current10
Interrupted Current Level #10
Only available if:Bwear Curve Fc = Active
0.00 - 2000.00kA
25.00kA
[Control
/Bkr
/Bwear]
Count10
Open Counts Allowed #10
Only available if:Bwear Curve Fc = Active
1 - 32000
30
[Control
/Bkr
/Bwear]
www.eaton.com
458
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...