![Eaton EMR-5000 Скачать руководство пользователя страница 459](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919459.webp)
EMR-5000
IM02602012E
Breaker Wear Signals (Output States)
Signal
Description
Operations Alarm
Signal: Service Alarm, too many Operations
Isum Intr trip: IA
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IA
Isum Intr trip: IB
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IB
Isum Intr trip: IC
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded: IC
Isum Intr trip
Signal: Maximum permissible Summation of the interrupting (tripping) currents exceeded in at
least one phase.
Res TripCmdCr
Signal: Resetting of the Counter: total number of trip commands
Res Isum trip
Signal: Reset summation of the tripping currents
WearLevel Alarm
Signal: Breaker Wear curve Alarm
WearLevel Lockout
Signal: Breaker Wear Curve Lockout Level
Res Bwear Curve
Signal: Reset of the Breaker Wear maintenance curve.
Isum Intr ph Alm
Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
Res Isum Intr ph Alm
Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has been exceeded".
Breaker Wear Counter Values
Value
Description
Default
Size
Menu path
TripCmd Cr
Counter: Total number of trips of the switchgear
(breaker, load break switch…). Resettable with
Total or All.
0
0 - 200000
[Operation
/Count and RevData
/Control
/Bkr]
Breaker Wear Values
Value
Description
Default
Size
Menu path
Isum trip IA
Summation of the tripping currents phase
0.00A
0.00 - 1000.00A [Operation
/Count and RevData
/Control
/Bkr]
www.eaton.com
459
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...