EMR-5000
IM02602012E
Copying Setting Groups (Parameter Sets) Via
PowerPort-E
Setting groups can only be copied if there are no conflicts (no red question
marks).
For applications using multiple settings groups, one can use the configuration file from the first group to create the
second group. With the help of
PowerPort-E,
the User can simply copy an existing setting group to another (not yet
configured) one. The User only needs to change those parameters where the two setting groups are different.
To efficiently establish a second parameter set where only few parameters are different, proceed as follows.
If
PowerPort-E
is not running, please start the application.
Open a (off-line) parameter file of a device or load data of a connected device.
Carefully save the relevant device parameters by selecting [File\Save as].
Select »Copy Parameter Sets« out of the “Edit” menu.
Then define both source and destination of the parameter sets to be copied (source = copy from; destination: copy
to).
Click on »OK« to start the copy procedure.
The copied parameter set is now cached (not yet saved!).
Then, modify the copied parameter set(s), if applicable.
Assign a new file name to the revised device parameter file and save it on your hard disk (backup copy).
To transfer the modified parameters back to the device, click on the »Device« menu item and select »Transfer All
Parameters into the Device«.
Comparing Setting Groups Via
PowerPort-E
If
PowerPort-E
is not running, please start the application.
Click on menu item »Edit« and select »Compare Parameter Sets«.
Select the two parameter sets from the two drop down menus that are to be compared with each other.
Press the »Compare« button.
The values that are different from the set parameters will be listed in tabular form.
www.eaton.com
393
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...