EMR-5000
IM02602012E
Global Protection Parameters of the System
Parameter
Description
Setting range
Default
Menu path
PSet-Switch
Switching Parameter Set
PS1,
PS2,
PS3,
PS4,
PSS via Inp fct,
PSS via Comm
PSS via Inp fct
[Protection Para
/PSet-Switch]
PS1: Activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case there is more than one input
function active, no Parameter Setting Group Switch will
be executed. In case all input functions are inactive, the
device will keep working with the Setting Group that was
activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
Sys.Maint Mode
Inactive
[Protection Para
/PSet-Switch]
PS2: Activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case there is more than one input
function active, no Parameter Setting Group Switch will
be executed. In case all input functions are inactive, the
device will keep working with the Setting Group that was
activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
Sys.Maint Mode
Active
[Protection Para
/PSet-Switch]
PS3: Activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case there is more than one input
function active, no Parameter Setting Group Switch will
be executed. In case all input functions are inactive, the
device will keep working with the Setting Group that was
activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
PS4: Activated by
This Setting Group will be the active one if: The
Parameter Setting Group Switch is set to "Switch via
Input" and the other three input functions are inactive at
the same time. In case there is more than one input
function active, no Parameter Setting Group Switch will
be executed. In case all input functions are inactive, the
device will keep working with the Setting Group that was
activated lastly.
Only available if: PSet-Switch = PSS via Inp fct
1..n, PSS
-.-
[Protection Para
/PSet-Switch]
www.eaton.com
316
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...