IM02602012E
Voltage Controlled Overcurrent Protection [51C]
When a sort circuit is near the generator, the voltage might drop down. By means of
Adaptive Parameters (Please
refer to chapter Parameter) the tripping times or tripping characteristics can be modified by the output signal of a
voltage element (depending on a threshold). The device might change a load curve to a fault curve (taking influence on
tripping time, trip curves and reset modes).
Please proceed as follows:
Read and understand the section „Adaptive Parameters“ within the chapter Parameter.
Do the device planning and set all required parameters for the Undervoltage element.
Do the device planning and set all required parameters for the Overcurrent element.
Set the
Adaptive Parameters within the Overcurrent element in the relevant parameter sets (e.g. Curve multiplier,
curve type...).
Assign the Undervoltage alarm (pickup) within the
Global Parameters as an activation signal for the corresponding
Adaptive Parameter set of the overcurrent element that should be modified.
Check the functionality by a commissioning test.
www.eaton.com
567
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...