EMR-5000
IM02602012E
Frequency measurement
Nominal frequency:
50 Hz / 60 Hz
Precision:
±0.05% of fn within the range of 40-70 Hz at voltages >50 V
Voltage dependency:
frequency acquisition from 0.15 x Vn
Energy measurement*
Energy counter error
1.5% of measured energy or 1.5% Sn*1h
Power Measurement*
VA, W, VAr:
<±1% of the measured value or 0.1% Sn (for fundamental)
<±2% of the measured value or 0.1% Sn (for RMS)
Power Factor Measurement*
PF:
±0.01 of measured power factor or 1°
I > 30% In and S >2% Sn
*)Tolerance at 0.8 … 1.2 x Vn (with Vn=100V) , |PF|>0.5, symmetrically feeded
Sn=1.73 * VT rating * CT rating
www.eaton.com
946
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...