EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
VRestraint max
Maximum voltage restraint level. Definition of Vn: Vn is
dependent on the System Parameter setting of "Main VT
con". When the System Parameters "Main VT con" is set
to "Open-Delta" , "Vn = Main VT sec ". When the System
Parameters "Main VT con" is set to "Wye", "Vn = Main VT
sec/SQRT(3)".
Only available if: VRestraint = Active
0.04 - 1.30Vn
1.00Vn
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
LOP Blo
Activates the use of the measuring circuit supervision. In
this case the module will be blocked if a measuring circuit
supervision module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse failure).
Only available if: VRestraint = Active
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/51P[1]]