EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Aux2 t-Delay
Auxiliary 2 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function2 =
Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
Aux2 Trip
Auxiliary 2 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function2 = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
WD Alarm Function Winding Alarm Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Trip Function
Winding Trip Function
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Alarm
Winding Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function = Use
0 - 200°C
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD t-Delay
Winding If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function = Use
0 - 360min
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
WD Trip
Winding Threshold for Temperature Trip
Only available if: Device Planning: Trip Function = Use
0 - 200°C
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/WD Group]
www.eaton.com
771
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...