EMR-5000
IM02602012E
Set Parameters of the Power Factor Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
PF-55D[1]:
Inactive
PF-55D[2]: Active
PF-55A[1]:
Inactive
PF-55A[2]: Active
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trig Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Trigger-PF
This is the power factor where the relay will pick up
0.5 - 0.99
0.7
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
Res Mode
Trigger Mode. Should the Module be triggered if the
Current Phasor is leading to the Voltage Phasor = Lead?
Or should the Module be triggered if the Current Phasor
is lagging to the Voltage Phasor = Lag?
leading,
lagging
lagging
[Protection Para
/<1..4>
/Power Factor-Prot
/PF-55D[1]]
www.eaton.com
738
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...