![Eaton EMR-5000 Скачать руководство пользователя страница 420](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919420.webp)
EMR-5000
IM02602012E
Supervision of the CLOSE command
When an CLOSE command is initiated, the »
t-Move CLOSE« timer will be started. While the timer is running, the »POS
I
NDETERM
« State will become true. If the command is executed and properly fed back from the switchgear before the
timer has run down, »POS CLOSE« will become true. Otherwise, if the timer has expired »POS D
ISTURB
« will become
true.
Supervision of the OPEN command
When an OPEN command is initiated, the »
t-Move OPEN« timer will be started. While the timer is running, the »POS
I
NDETERM
« State will become true. If the command is executed and properly fed back before the timer has run down,
»POS OPEN« will become true. Otherwise, if the timer has expired »POS D
ISTURB
« will become true.
The following table shows how switchgear positions are validated:
States of the Digital Inputs
Validated Breaker Positions
Aux CLOSE-I
Aux OPEN-I
POS CLOSE POS OPEN
POS
Indeterm
POS Disturb
POS
State
0
0
0
0
1
(while a Moving
timer is running)
0
(while a Moving
timer is running)
0
Intermediate
1
1
0
0
1
(while a Moving
timer is running)
0
(while a Moving
timer is running)
0
Intermediate
0
1
0
1
0
0
1
OPEN
1
0
1
0
0
0
2
CLOSE
0
0
0
0
0
(Moving timer
elapsed)
1
(Moving timer
elapsed)
3
Disturbed
1
1
0
0
0
(Moving timer
elapsed)
1
(Moving timer
elapsed)
3
Disturbed
www.eaton.com
420
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...