![Eaton EMR-5000 Скачать руководство пользователя страница 594](http://html1.mh-extra.com/html/eaton/emr-5000/emr-5000_installation-operation-and-maintenance-manual_3985919594.webp)
EMR-5000
IM02602012E
Setting Group Parameters of the 50X Ground Fault Protection
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Active
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
Rvs Blo Fc
Activate (allow) or inactivate (disallow) reverse blocking
of the module/element. This parameter is only effective if
a signal is assigned to the corresponding global
protection parameter. If the signal becomes true, those
modules/element are blocked that are parameterized
"Rvs Blo Fc = active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
Inactive,
Active
50X[1]: Inactive
50X[2]: Active
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
Criterion
Measuring method: fundamental or rms or 3rd harmonic
(only generator protection relays)
Fundamental,
True RMS
True RMS
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
Pickup
If the pickup value is exceeded, the module/element will
be started.
0.02 - 20.00In
50X[1]: 1In
50X[2]: 2In
[Protection Para
/<1..4>
/I-Prot
/50X[1]]
www.eaton.com
594
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...