EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
EMGOVR
Emergency override options. Signal has to be active in
order to release the thermal capacity of the motor. Please
notice that by doing this you run the risk of damaging the
motor. “EMGOVR” has to be set to “DI” or “DI or UI” for
this input to take effect.
Inactive,
DI,
UI,
DI or UI
Inactive
[Protection Para
/Global Prot Para
/MStart
/Start Control]
RemStartBlock
Remote Motor Start Blocking
Only available if: RemStartBlo Fc = Active
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
EmgOvr
Emergency Override. Signal has to be active in order to
release the thermal capacity of the motor. Please notice
that by doing this you run the risk of damaging the motor.
“EMGOVR” has to be set to “DI” or “DI or UI” for this input
to take effect
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
INSQ
INcomplete SeQuence
Only available if: INSQReportFrom = Active
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
ZSS
Zero Speed Switch
Only available if: ZSS = Active
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
STPC Blo
With this setting a Digital Input keeps the Motor in the
RUN mode, even when the motor current drops below
STPC (motor stop current).
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/MStart
/Motor Inputs]
t-Blo-IOC
Phase Instantaneous Overcurrent Start Delay. 50P[x]
elements are blocked for the time programmed under this
parameter, while the motor is starting.
0.03 - 1.00s
0.05s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
t-Blo-GOC
Ground Instantaneous Overcurrent Start Delay. 50X[x],
50R[x] and 50G[x] elements are blocked for the time
programmed under this parameter, while the motor is
starting
0.03 - 1.00s
0.08s
[Protection Para
/Global Prot Para
/MStart
/Start Delay Timer]
www.eaton.com
494
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...