Criterion - Measuring Mode
For all protection elements it can be determined, whether the measurement is done on basis of the »
Fundamental« or if
»
TrueRMS« measurement is used.
Voltage restraint overcurrent protection 51V
When the Parameter »
VRestraint« is set to active the overcurrent protection element works voltage restraint. That
means, the overcurrent pickup threshold will be lowered during voltage drops. This results in a more sensitive
overcurrent protection. For the voltage threshold »
VRestraint max« additionally the »Measuring Channel« can be
determined.
All 51P overcurrent protective elements can be planned as non-directional or optionally as directional elements. This
means, all 6 elements can be planned user defined in forward/reverse or non directional.
For each element the following characteristics are available:
NINV (IEC/AMZ)
VINV (IEC/AMZ)
LINV (IEC/AMZ)
EINV (IEC/AMZ)
MINV (ANSI/AMZ)
VINV (ANSI/AMZ)
EINV (ANSI/AMZ)
Thermal Flat
IT
I2T
I4T
For tripping curves please refer to the “Appendix/Time Current Curves (PHASE)” section.
By using the projecting parameters each of the overcurrent protective elements can be defined as
»forward«,
»reverse« or »non-directional«. The forward or reverse direction is based on the characteristic angle for the phase
direction specified by the field parameter
»I MTA«. No directional information will be taken into account if the current
protective element is planned as
»non-directional«
www.eaton.com
553
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...