EMR-5000
IM02602012E
Parameter
Description
Setting range
Default
Menu path
Aux2
Auxiliary2
No,
Yes
No
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting1]
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
Voting 2
Voting: This parameter defines how many of the selected
channels must be over its threshold level for getting a
voting trip
1 - 12
1
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
WD 1
Winding 1
No,
Yes
No
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
WD 2
Winding 2
No,
Yes
No
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
WD 3
Winding 3
No,
Yes
No
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
WD 4
Winding 4
No,
Yes
No
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Voting2]
www.eaton.com
776
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...