EMR-5000
IM02602012E
Setting Group Parameters of the Trip Circuit Monitoring Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/TCM]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/TCM]
t-TCM
Tripping delay time of the Trip Circuit Supervision
0.10 - 10.00s
0.2s
[Protection Para
/<1..4>
/Supervision
/TCM]