EMR-5000
IM02602012E
Analog Outputs
The following technical data only apply to devices, which are equipped with analog outputs. Please refer to the order
code of your device.
The mode of each output can be individually selected between current or voltage output. Shielded cable for the analog
outputs is recommended. The terminals of the HF shield should be used, when connecting the shield to ground on both
sides of the cable is not possible. On one side of the cable the shield has to be directly connected to ground. In case of
the use of unshielded twisted pair cables, the length must not exceed 10 m. All analog outputs have a common potenti-
al. Each output has an own common terminal.
Current mode
Range:
Max. load resistance:
0-20 mA
1 k
Ω
Voltage mode
Range:
0-10 V maximum output current 1 mA
Accuracy
0.5% of the nominal value 20 mA resp. 10 V
Influence of temperature to accuracy
<1% (within the range of 0°C to +60°C (+32°F to +140°F)
Test voltage of outputs (one group)
against other electrical groups
Test voltage of outputs (one group)
against ground
2.5 kV
1.0 kV
www.eaton.com
936
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...