EMR-5000
IM02602012E
Modbus TCP
Establishing a connection via TCP/IP to the device is only possible if the device
is equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: Setting the TCP/IP Parameters
Call up
»Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:
TCP/IP address;
Subnetmask; and
Gateway.
Part 2: Configuration of the Devices
Call up
»Device parameter/Modbus« and set the following communication parameters.
Setting a unit identifier is only necessary if a TCP network should be coupled to a RTU network.
If a different port than the default port 502 should be used, please proceed as follows:
Choose “Private” within the TCP-Port-Configuration.
Set the port number.
Set the maximum acceptable time out for “no communication”. If this time has expired without any
communication, the device concludes a failure has occurred within the master system.
Allow or disallow the blocking of SCADA commands.
Part 3: Hardware Connection
There is a RJ45 interface at the rear side of the device for the hardware connection to the control system.
Establish the connection to the device by means of a proper Ethernet cable.
www.eaton.com
323
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...