EMR-5000
IM02602012E
Generation/Export of a Device Specific ICD File
Each Eaton IEC 61850 capable device includes a description of its own functionality and communications skills in the
form of an IED Capability Description (*.ICD) file. This file can be exported as follows and be used for the configuration
of the substation.
•
A change of the devices parameters has an influence on the content of
the ICD file.
1. Connect the device with your PC/Notebook.
2. Start PowerPort E.
3.
Click on »
Receive data from Device«
in the »
Device« menu.
4.
Click on
»
IEC 61850«
in the »
Device Para« menu.
5. Click on the ICD icon in the IEC 61850 window.
6. Select a drive and file name for the ICD file and click "save".
7. Repeat the steps 1 to 6 for all connected devices in this IEC 61850 environment.
Generation/Export of a SCD file
Each device can create an export it's own functionality and communications skills in form of a *.SCD file.
1. Connect the device with your PC/Notebook.
2. Start Power-Port-E.
3.
Click on »
Receive data from Device«
in the menu »
Device«.
4.
Click on
»
IEC61850«
in the menu »
Device Para«.
5. Click on the SCD icon in the IEC61850 window.
6. Select a drive and file name for the SCD file and click "save".
7. Repeat the steps 1 to 6 for all connected devices in this IEC61850 environment.
Generation of a Substation Configuration Description (SCD) File
The substation configuration (i. e. connection of all logical nodes of protection and control devices) as well as switch
gear usually is done with a ”Substation Configuration Tool“. Therefore the ICD files of all connected IEDs in the IEC
61850 environment have to be available. The result of the station wide “software wiring” can be exported in the form of
a Station Configuration Description (SCD) file.
Suitable Substation Configuration Tools (SCT) are available by the following Companies:
H&S, Hard- & Software Technologie GmbH & Co. KG, Dortmund (Germany) (
).
Applied Systems Engineering Inc. (
Kalki Communication Technologies Limited (
www.eaton.com
330
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...