EMR-5000
IM02602012E
DI-8P X
Name of the Assembly group:
DI-8P X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Setting range
Default
Menu path
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Inverting 1
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Debouncing Time 1 A change of the state of a digital input will only be
recognized after the debouncing time has expired
(become effective). Thus, transient signals will not be
misinterpreted.
No Debouncing
Time,
20 ms,
50 ms,
100 ms
20 ms
[Device Para
/Digital Inputs
/DI-8P X1
/Group 1]
Nom Voltage
Nominal voltage of the digital inputs
24 V dc,
48 V dc,
60 V dc,
110/120 V dc,
230/240 V dc,
110/120 V ac,
230/240 V ac
110/120 V dc
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
Inverting 2
Inverting the input signals.
Inactive,
Active
Inactive
[Device Para
/Digital Inputs
/DI-8P X1
/Group 2]
www.eaton.com
76
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...