EMR-5000
IM02602012E
System Contact and IRIG-B00X
Make sure that the tightening torque is 5-7 In-lb [0.56-0.79 Nm].
Terminals
Pin Assignment for Device
The Supervision Contact (SC) closes after the boot phase of the device if the protection is working. This Supervision
Contact (SC) will open if an internal device error has occurred (please refer to the Self Supervision section).
The
System-OK contact (SC relay)
cannot be configured. The system contact is a Form “C” contact that picks up when
the device is free from internal faults. While the device is booting up, the
System OK relay (SC)
remains dropped-off
(unenergized). As soon as the system is properly started, the System Contact picks up and the assigned LED “Opera-
tional” is activated accordingly (please refer to the Self Supervision section).
www.eaton.com
69
1
X
10
4
2
3
4
5
S
C
IR
IG
-B
+
IR
IG
-B
-
X104
1
3
2
4 5
S
C
N
.C
.
S
C
N
.O
.
S
C
C
M
N
IR
IG
-B
+
IR
IG
-B
-
Содержание EMR-5000
Страница 62: ...EMR 5000 IM02602012E Ethernet RJ45 Terminal Marking www eaton com 62 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 271: ...EMR 5000 IM02602012E Fault Recorder Module Signals Signal Description Res record Signal Delete Record www eaton com 271...
Страница 524: ...EMR 5000 IM02602012E Motor Protection Curves Motor Protection Curve Example 1 www eaton com 524...
Страница 525: ...EMR 5000 IM02602012E Motor Protection Curve Example 2 without RTDs www eaton com 525...
Страница 526: ...EMR 5000 IM02602012E Motor Protection Curve Example 3 with RTDs www eaton com 526...
Страница 930: ...EMR 5000 IM02602012E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 930...