WHITE-RODGERS
T
T
X
X
1
2
3
4
2
Printed in U.S.A.
PART NO. 37-2744C
Replaces 37-2744B
0125
TYPE 829A-832
RELAY
For Use With Low Voltage Thermostats
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, Fax (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
R
DESCRIPTION
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.
Type 829A-832 Relay has double-pole, single-throw
switch action.
This Relay permits the use of a sensitive low voltage
thermostat to control a line voltage heating or cooling
load. It is especially suitable for use on hot water heating
systems, and may be used for boilers with tankless
domestic coil as well as for boilers without a domestic
coil.
DOTTED LINES
INDICATE FIELD
WIRING
Fig. 1
TO MILLIVOLT VALVE OR
LOW VOLTAGE LOAD
RELAY
COIL
HOT
LINE
N
PRECAUTIONS
To prevent electrical shock and/or equipment
damage, disconnect electric power to system, at
main fuse or circuit breaker box, until installation
is complete.
If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and
air conditioning contractor, electrician, or someone famil-
iar with basic electricity and wiring.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
CAUTION
Do not use on circuits exceeding specified
voltages. Higher voltages will damage control
and could cause shock or fire hazard.
WARNING
ELECTRICAL DATA
Switch Action: Double-Pole, Single-Throw, normally open
Input Voltage: Terminals (1 & 2) 120V.A.C., 60Hz
Room Thermostat:
Set adjustable heat anticipator at 0.3 Amps. For fixed
anticipation thermostats, use 0.25 to 0.35 Amp. heater.
Rating:
Terminals X-X millivolt
1 volt D.C. max. 1 amp D.C. max. or
30V.A.C. max. @ 1 amp max.
Terminals (3 & 4)
Motor: 120V.A.C.
8F.L.A.
48L.R.A.
240V.A.C.
4F.L.A.
24L.R.A.
SPECIFICATIONS
PRINCIPLE OF OPERATION
The 829A-832 relay is provided with a self-contained
transformer with a low voltage secondary output for
energizing the relay coil.
Line voltage lines should be connected to terminals
marked “1 & 2” for power to reach the transformer.
Closing the thermostat circuit energizes the relay coil
which in turn closes the circuit between terminals 1 and
3 and 1 and 4, also closing millivolt or low voltage circuit
between X and X.
Opening the thermostat circuit de-energizes the relay
coil, breaking the circuit between terminals 1 and 3 and
1 and 4, also breaking millivolt or low voltage circuit
between X and X.